Rating/Performance
noumenon
Sensor parts F3ZN-S□□□□N□□-(01~05) are common
Item model
F3ZN-S□□□□N09
F3ZN-S□□□□N15
F3ZN-S□□□□N30
F3ZN-S□□□□N60
Detection distance
0.2~7m
0.2~10m
Optical axis spacing
9mm
15mm
30mm
60mm
Optical axis number
21~125
13~120
7~60
4~30
Detection width
180~1,116mm
180~1,785mm
180~1,770mm
240~1,740mm
Minimum detection object (opaque)
Diameter φ14mm
Diameter φ25mm
Diameter φ40mm
Diameter φ70mm
Light source (luminous wavelength)
Infrared Light Emitting Diode (870nm)
Supply voltage
DC24V± 10% pulse (p-p) less than 10%
Consumption current
Floodlight: 170mA or less, Receiver: 120mA or less
Control output
Load supply voltage DC 24V or less, NPN transistor output (load current 50mA or less) Control output 1: ON when light enters, control output 2: ON when light is blocked (initial setting at the factory)
External diagnostic function
External diagnostic input line 0~1.5V: Flood light stops (short circuit current 3mA or less) When external diagnostic output line is open or 9~24V: Normal beaming
Display light
floodlight
Illumination level indicator light 5 LEDs (green): Lights up according to light exposure Error mode display light 3 LEDs (red): Lights up according to what happened when an abnormality occurs Power display light (green): Normally on, turns off when an abnormality occurs External diagnostic display light (orange): Lights up when external diagnosis occurs
Receiver
Illumination level indicator light 5 LEDs (green): Illuminates according to the amount of light received Error mode indicator light 3 LEDs (red): Illuminates according to the occurrence in the event of an abnormality Control output 1 Action display light (orange): Illuminates when light enters Control output 2 Action display light (orange): illuminates when shading (initially set at the factory) Power indicator light (green): Normally on, turns off when an abnormality occurs Function indicator light (green): Lights on when set to open
Protection circuit
Power supply reverse connection protection, output short circuit protection
Answer time
For details, please refer to page 683 of →
Use ambient temperature
Incandescent lamp: less than 3,000 lx, sunlight: less than 10,000 lx
ambient temperature
During operation: -10~+55°C, when stored: -30~+70°C (no freezing or condensation)
ambient humidity
When acting/saving: 30~95% RH each (non-condensing)
Insulation impedance
20MΩ or more (DC500V megaohmmeter)
Withstand voltage
AC1,000V 50/60Hz 1min
Vibration (malfunction)
10~55Hz rejuvenation amplitude 0.7mm X, Y, Z directions 20 scans
Impact (Malfunction)
100m/s2 1,000 times in each direction of X, Y, and Z
Protect the structure
IEC specification IP65
Connection
M12 connector internal
Quality (Bundle Status)
Mass (g) = (Detection width +100) × 2+2,100
Material
enclosure
aluminium
Front cover
Propyl dilute (PMMA resin)
line
Oil-resistant PVC
accessory
Metal mounting fittings (upper/lower), metal mounting fittings (middle)*, instruction manual
*Intermediate metal fittings are the inner molds that are attached only to the following. The total length is less than 640~1,280mm, and there is 1 set attached; Total length over 1,280mm: 2 sets
noumenon
Controller Division
Item model
F3ZP-M1N-FLK
Supply voltage
DC24V± 10% pulse (p-p) less than 10%
Consumption current
50mA or less (excluding sensor consumption current and output current)
Connect the sensor
F3ZN-S□□□□N□□
Number of sensor connections
1 set (3 sets or up to 240 optical axes: Recently)
Output[OUT1·2, OUTPUT(OUT3, ERROR, BANK OUT, TCHOUT)]
Load supply voltage DC 24V or less, NPN open connector output (load current 50mA or less)
Input (TCH, EDI, RESET, BANKIN, BANK1, BANK2)
DC Input Maximum Input Voltage: 24V±10% Operating Voltage ON Voltage: Min. 9V/OFF Voltage: Max. 1.5V, Input Current 3mA or less
Programmable input and export
(D00~D15) Depending on the application, the purpose of use is different. Output: Load supply voltage DC 24V or less, NPN open connector output (load current 50mA or less) Input: DC input input voltage: 24V±10% input current 3mA or less Operating voltage ON voltage: minimum 9V/OFF Voltage: maximum 1.5V
Communication function
Communication port
RS-232C □ (D-SUB 9 pin connector), RS-485□ (terminal block) (you can choose either side with the transfer switch)
Communication Regulations
CompoWay/F
Machine No.
00~15 (Set with rotary switch)
Communication speed
9600, 14400, 19200, 38400, 57600, 115200bps (switching conversion)
data structure
Data bit 7, odd and even number, start bit 1, start bit 2, no flow control
Time function
Year/month/day/hour/minute/second/week
Display light
POWER: green, MODE: green, RUN: green: ERROR: red
Protection circuit
Power supply reverse connection protection, output short circuit protection
Answer time
For details, please refer to page 683 of →
ambient temperature
When using: -10~+55°C, when stored: -20~+75°C (no freezing, condensation)
ambient humidity
When using and storing: 10~90%RH (non-condensing)
Insulation impedance
Total 20MΩ or more (DC500V megaohm meter) Full terminal-to-housing room
Withstand voltage
AC1,000V 50/60Hz 1 min leakage current less than 10mA
Vibration (durable)
Refer to JIS C0041 10~57Hz Amplitude 0.075mm 57~150Hz Acceleration 9.8m/s2 X, Y, Z directions 80 minutes (8 minutes during scanning× 10 scans = 80 minutes in total)
Impact (Durable)
Refer to JIS C0041 147m/s2 X, Y, and Z directions 3 times each
structure
In-disk type
accessory
RS-232C connector (latch, cover), instruction manual
|