LC1-D1801M7N
1. Scope of application
LC1D series AC contactor (hereinafter referred to as contactor) is suitable for AC 50Hz or 60Hz, voltage to 660V, current to 95A circuit, for remote connection and breaking circuit, frequent starting, control AC motor, contactor can also be assembled into building block auxiliary contact group, air delay head, mechanical interlock mechanism and other accessories, composed of delay contactor, reversible contactor, star delta starter, And can be with appropriate products in accordance with IEC60947-4-1 and GB14048.4 standards.
Second, the model and its meaning
3. Normal working conditions and installation conditions//www.chip100.com/
3.1 The ambient air temperature is: -5°C~+40°C. its average value within 24 hours does not exceed +35°C;
3.2 Altitude: not more than 2000m;
3.3 Atmospheric conditions: the relative humidity of the air does not exceed 50% at +40 °C, there can be higher relative humidity at lower temperatures, the average minimum monthly temperature of the wettest month does not exceed +25 °C, and the monthly average maximum relative humidity of the month does not exceed 90%, and consider the condensation that occurs on the product due to temperature changes.
3.4 Pollution level: 3;
3.5 Installation category: Class III;
3.6 Installation conditions: the inclination of the mounting surface and the vertical surface is not more than ±5°;
3.7 Shock and vibration: The product should be installed and used in a place free of significant shaking, shock and vibration.
Fourth, the main parameters and technical performance
4.1 The contactor can be assembled with any of the accessories in Table 1 and Table 2
Auxiliary contact group
Table 1
Model
|
Number of contacts
|
F4-02
|
2NC
|
F4-11
|
1NO+1NC
|
F4-20
|
2NO
|
F4-22
|
2NO+2NC
|
F4-40
|
4NO
|
F4-04
|
4NC
|
F4-13
|
1NO+3NC
|
F4-31
|
3NO+1NC
|
Air delay head
Table 2
Model
|
Delay range
|
Number of delay contacts
|
LA2-D20
|
0.1s~3s
|
1NO+1NC
|
LA2-D22
|
0.1s~30s
|
1NO+1NC
|
LA2-D24
|
10s~180s
|
|
LA3-D20
|
0.1s~3s
|
1NO+1NC
|
LA3-D22
|
0.1s~30s
|
1NO+1NC
|
LA3-D24
|
10s~180s
|
1NO+1NC
|
4.2 Main parameters and technical performance indicators of contactors (see Table 3)
Table 3
Model
|
(CJX2)LC1D-09
|
(CJX2)LC1D-12
|
(CJX2)LC1D-18
|
(CJX2)LC1D-25
|
(CJX2)LC1D-32
|
(CJX2)LC1D-40
|
(CJX2)LC1D-50
|
(CJX2)LC1D-63
|
(CJX2)LC1D-80
|
(CJX2)LC1D-95
|
rated Job current (A)
|
380V
|
AC-3
|
9
|
12
|
18
|
25
|
32
|
40
|
50
|
63
|
80
|
95
|
AC-4
|
3.5
|
5
|
7.7
|
8.5
|
12
|
18.5
|
24
|
28
|
37
|
44
|
660V
|
AC-3
|
6.6
|
8.9
|
12
|
18
|
21
|
34
|
39
|
42
|
49
|
49
|
AC-4
|
1.5
|
2
|
3.8
|
4.4
|
7.5
|
9
|
12
|
14
|
17.3
|
21.3
|
Agreed heating current (A)
|
20
|
20
|
32
|
40
|
50
|
60
|
80
|
80
|
110
|
110
|
Agreed heating voltage (V)
|
660
|
660
|
660
|
660
|
660
|
660
|
660
|
660
|
660
|
660
|
Controlled three-phase squirrel cage Motor power (AC-3)kW
|
220V
|
2.2
|
3
|
3
|
5.5
|
7.5
|
11
|
15
|
18.5
|
22
|
25
|
380V
|
4
|
5.5
|
5.5
|
11
|
15
|
18.5
|
22
|
30
|
37
|
45
|
660V
|
5.5
|
7.5
|
7.5
|
15
|
18.5
|
30
|
37
|
37
|
45
|
45
|
operate frequency (times/h)
|
Electrical life
|
AC-3
|
1200
|
1200
|
1200
|
1200
|
600
|
600
|
600
|
600
|
600
|
600
|
AC-4
|
300
|
300
|
300
|
300
|
300
|
300
|
300
|
300
|
300
|
300
|
Mechanical life
|
3600
|
3600
|
3600
|
3600
|
3600
|
3600
|
3600
|
3600
|
3600
|
3600
|
Electrical life (10,000 times)
|
AC-3
|
100
|
100
|
100
|
100
|
80
|
60
|
60
|
60
|
60
|
60
|
AC-4
|
20
|
20
|
20
|
20
|
20
|
15
|
15
|
15
|
10
|
10
|
Mechanical life (10,000 times)
|
1000
|
1000
|
1000
|
1000
|
800
|
800
|
800
|
800
|
600
|
600
|
Fuse model is available
|
RT16-20
|
RT16-20
|
RT16-32
|
RT16-40
|
RT16-50
|
RT16-63
|
RT16-80
|
RT16-80
|
RT16-100
|
RT16-125
|
Cold-pressed ends
|
Cord with cold-pressed ends
|
root
|
1~2
|
1~2
|
1~2
|
1 2
|
1 2
|
1 2
|
1 2
|
1 2
|
1 2
|
1 2
|
The cord does not have a cold pressed end Hard wire
|
mm2
|
2.5
|
2.5
|
4
|
4 4
|
4 4
|
10 10
|
16 16
|
16 16
|
50 25
|
50 25
|
4
|
4
|
6
|
10 6
|
10 6
|
16 10
|
25 16
|
25 16
|
50 35
|
50 35
|
4
|
4
|
6
|
6 6
|
6 6
|
10 10
|
25 -
|
25 -
|
50 -
|
50 -
|
coil power
|
50Hz
|
Suction (VA)
|
70
|
70
|
70
|
110
|
110
|
200
|
200
|
200
|
200
|
200
|
Hold (VA)
|
8
|
8
|
8
|
11
|
11
|
20
|
20
|
20
|
20
|
20
|
|
Power(W)
|
1.8~2.7
|
1.8~2.7
|
1.8~2.7
|
3~4
|
3~4
|
6~10
|
6~10
|
6~10
|
6~10
|
6~10
|
Range of motion
|
The pull-in voltage is: 85%~110%Us; The release voltage is 20%~75%Us
|
Basic parameters of auxiliary contacts
|
AC-15:360VA DC-13:33W Ith:10A
|